摘要
A synchronous control system is designed to observably raise the success rate of synthetic test of circuit breaker. First, a hardware circuit of the synchronous control system is designed. Second, considering the source current is approximately linear in the zero area, the current model is simplified, and a program for predicting current zero is coded. According to the test data, the error between actual trigger time and setting time of the voltage circuit is less than 50 μs, and the error between actual trigger time and setting time of the arc prolonging circuit is less than 40 μs. The errors meet the design requirements, and can ensure the equivalence of the synthetic test, thus the performance of the synchronous control system is verified.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 152-157 |
| 页数 | 6 |
| 期刊 | Gaoya Dianqi/High Voltage Apparatus |
| 卷 | 51 |
| 期 | 8 |
| DOI | |
| 出版状态 | 已出版 - 16 8月 2015 |