TY - JOUR
T1 - Rotor Loss and Temperature Field of Synchronous Condenser Under Single-Phase Short-Circuit Fault Affected by Different Materials of Rotor Slot Wedge
AU - Xu, Guorui
AU - Hu, Peidong
AU - Li, Zhiqiang
AU - Zhao, Haisen
AU - Zhan, Yang
N1 - Publisher Copyright:
© 1972-2012 IEEE.
PY - 2022
Y1 - 2022
N2 - A synchronous condenser (SC) can provide the dynamic reactive power for the ultra-high-voltage direct current converter station during the system voltage drop caused by the single-phase short-circuit fault, which is one of the prevalent faults. However, the single-phase short-circuit fault can also result in the increase of the rotor loss and temperature and thus restrict the transient operating ability of the SC. A key factor that affects the rotor loss and temperature rise is the material of the rotor slot wedges. For a 300-MVar SC with the rotor slot wedges made of the aluminum, beryllium bronze, and stainless steel, the rotor loss and temperature distribution under the single-phase short-circuit are calculated by coupling the electromagnetic and temperature field models of the SC with the models of the power grid. The variations of the rotor losses along with the rotor slot wedge conductivity are revealed. The rotor regions, where the highest temperature rise appears, are obtained. According to the maximum permissible temperature of the rotor material, the transient operating ability of the SC withstanding the single-phase short-circuit fault is obtained. This article can provide the theoretic basis for improving the transient operating ability of the SC.
AB - A synchronous condenser (SC) can provide the dynamic reactive power for the ultra-high-voltage direct current converter station during the system voltage drop caused by the single-phase short-circuit fault, which is one of the prevalent faults. However, the single-phase short-circuit fault can also result in the increase of the rotor loss and temperature and thus restrict the transient operating ability of the SC. A key factor that affects the rotor loss and temperature rise is the material of the rotor slot wedges. For a 300-MVar SC with the rotor slot wedges made of the aluminum, beryllium bronze, and stainless steel, the rotor loss and temperature distribution under the single-phase short-circuit are calculated by coupling the electromagnetic and temperature field models of the SC with the models of the power grid. The variations of the rotor losses along with the rotor slot wedge conductivity are revealed. The rotor regions, where the highest temperature rise appears, are obtained. According to the maximum permissible temperature of the rotor material, the transient operating ability of the SC withstanding the single-phase short-circuit fault is obtained. This article can provide the theoretic basis for improving the transient operating ability of the SC.
KW - Rotor slot wedge material
KW - rotor temperature rise
KW - single-phase short-circuit fault
KW - synchronous condenser (SC)
UR - https://www.scopus.com/pages/publications/85136047049
U2 - 10.1109/TIA.2022.3197379
DO - 10.1109/TIA.2022.3197379
M3 - 文章
AN - SCOPUS:85136047049
SN - 0093-9994
VL - 58
SP - 7171
EP - 7180
JO - IEEE Transactions on Industry Applications
JF - IEEE Transactions on Industry Applications
IS - 6
ER -