跳到主要导航 跳到搜索 跳到主要内容

Performance Analysis of an Ejector-Enhanced Heat Pump System for Low-Temperature Waste Heat Recovery Using UHVDC Converter Valves

  • Menghan Jin
  • , Xingjuan Zhang*
  • , Jianhui Zhou
  • , Limin Zhang
  • *此作品的通讯作者
  • State Grid Corporation of China
  • State Key Lab of Advance Power Transmission Technology
  • Shandong Electric Power Research Institute

科研成果: 期刊稿件文章同行评审

摘要

This article proposes a heating method based on heat pump technology to address the large amount of low-grade waste heat generated by a certain type of ultra-high voltage direct current (UHVDC) converter valve. Thermal performance calculations for two systems, a basic vapor compression heat pump system (BVCHPS) based on thermal expansion valve throttling and an ejector-enhanced heat pump system (EEHPS) are analyzed. The research results show that the EEHPS exhibits superior COP and exergy efficiency when generating hot water above 80 °C using a heat source below 50 °C. Additionally, mathematical modeling analysis identifies optimal structural parameters such as nozzle throat diameter, throat area ratio, and nozzle outlet diameter for the ejector in its design state. The low-temperature waste heat recovered from the UHVDC converter valves can be further used in engineering applications such as heating, refrigeration, seawater desalination, and sewage treatment.

源语言英语
文章编号3589
期刊Energies
17
14
DOI
出版状态已出版 - 7月 2024

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

指纹

探究 'Performance Analysis of an Ejector-Enhanced Heat Pump System for Low-Temperature Waste Heat Recovery Using UHVDC Converter Valves' 的科研主题。它们共同构成独一无二的指纹。

引用此