摘要

Voltage fluctuation and flicker is an important aspect of power quality. The key of flicker analysis is to track the envelope of voltage signals and then calculate the short-term flicker severity. In this paper, a new method on calibration of flickermeters was presented. The method did not adopt the phase-locked loop between the flicker waveform generator and the DVM. It tracked the envelope by interpolated discrete Fourier transform to eliminate the measurement errors caused by the asynchronous sampling. The error of the new flickermeter calibration system was estimated to be about 10-5.

源语言英语
主期刊名2014 31th URSI General Assembly and Scientific Symposium, URSI GASS 2014
出版商Institute of Electrical and Electronics Engineers Inc.
ISBN(电子版)9781467352253
DOI
出版状态已出版 - 17 10月 2014