摘要
A lumped-parameter model was established for metal hydride cooling system, in which the plateau slope and hysteresis are considered. The working cycle of a metal hydride system using MmNi4.5Al0.5/MmNi4.2Al0.1Fe0.7, as working media was simulated and its performance was predicted. The effects of plateau slope, hysteresis, working temperatures and heat recovery on system performance were investigated. The results show that COP (coefficient of performance) of the system can reach 0.33 at the designing point, while the plateau slope and hysteresis have negative effects, and heat recovery can improve COP but would decrease the cooling power.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 488-492 |
| 页数 | 5 |
| 期刊 | Taiyangneng Xuebao/Acta Energiae Solaris Sinica |
| 卷 | 23 |
| 期 | 4 |
| 出版状态 | 已出版 - 8月 2002 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源