摘要

This paper experimentally investigates a parallel strip fin heat sink (PSFHS) with various types of inlet/outlet arrangements (IOAs) including I-type, L-type, and U-type. The heat sink contains 150 fins 1 mm wide and 5.5 mm high on a square in-line configuration with a 1 mm pitch. Nine thermocouples are placed inside the base plate of the heat sink to map the temperature distribution in it. Because of the difference in IOAs, the resultant temperature distributions are different. The corresponding boiling curves and flow pattern are discussed in detail. In addition, the two-phase thermal resistance and temperature uniformity are utilized to evaluate the thermal performance of the heat sink. The experiment results show that the inlet/outlet arrangements have a significant influence on local dry out and temperature distribution, both of which are also affected by the discontinuous passage configuration. It is found that L-type PSFHS has relatively small thermal resistance with a moderated temperature uniformity, and I-type PSFHS has the worst performance in temperature distribution.

源语言英语
文章编号115061
期刊Applied Thermal Engineering
176
DOI
出版状态已出版 - 25 7月 2020