TY - JOUR
T1 - Dependent Competing Failure Modeling for the GIL Subject to Partial Discharge and Air Leakage With Random Degradation Initiation Time
AU - Hao, Songhua
AU - Yang, Jun
N1 - Publisher Copyright:
© 2018 IEEE.
PY - 2019/9/1
Y1 - 2019/9/1
N2 - Confronted with the ever-growing demand for electricity delivery over long distances, the gas insulated transmission line (GIL), as an advanced underground technology, has been under rapid development recently. Physics-of-failure analysis for the GIL indicates that it experiences two competing failure modes: 1) Once the amount of air leakage is greater than a predetermined threshold level, a deterioration-based soft failure happens. 2) The arrival of a partial discharge with overlarge voltage will result in a shock-based hard failure. Furthermore, statistical analysis of some engineering projects shows that the beginning of the GIL degradation, i.e., the inner air begins to leak, occurs after an initiation time. In addition, the flashover voltage decreases considerably as the SF6 in the GIL leaks outside and the moisture penetrates inside, which reflects that the hard failure threshold level is related to the degradation process. Confronted with these problems, a new dependent competing failure model is presented for the GIL, with the consideration of degradation initiation time. The GIL reliability assessment is obtained through theoretical derivation, and the numerical calculation method with controllable approximation accuracy. Finally, a case study is carried out to show the implementation of the proposed model.
AB - Confronted with the ever-growing demand for electricity delivery over long distances, the gas insulated transmission line (GIL), as an advanced underground technology, has been under rapid development recently. Physics-of-failure analysis for the GIL indicates that it experiences two competing failure modes: 1) Once the amount of air leakage is greater than a predetermined threshold level, a deterioration-based soft failure happens. 2) The arrival of a partial discharge with overlarge voltage will result in a shock-based hard failure. Furthermore, statistical analysis of some engineering projects shows that the beginning of the GIL degradation, i.e., the inner air begins to leak, occurs after an initiation time. In addition, the flashover voltage decreases considerably as the SF6 in the GIL leaks outside and the moisture penetrates inside, which reflects that the hard failure threshold level is related to the degradation process. Confronted with these problems, a new dependent competing failure model is presented for the GIL, with the consideration of degradation initiation time. The GIL reliability assessment is obtained through theoretical derivation, and the numerical calculation method with controllable approximation accuracy. Finally, a case study is carried out to show the implementation of the proposed model.
KW - Air leakage
KW - degradation initiation time
KW - dependent competing failure
KW - partial discharges
KW - reliability model
KW - the gas insulated transmission line (GIL)
UR - https://www.scopus.com/pages/publications/85055885819
U2 - 10.1109/TR.2018.2875819
DO - 10.1109/TR.2018.2875819
M3 - 文章
AN - SCOPUS:85055885819
SN - 0018-9529
VL - 68
SP - 1070
EP - 1079
JO - IEEE Transactions on Reliability
JF - IEEE Transactions on Reliability
IS - 3
ER -