Abstract

This paper describes the arc behavior in the transverse-magnetic-field (TMF) contacts at intermediate frequency (400-800 Hz). With high-speed photography, three different arc modes were identified: expansion arc column, moving arc, and diffuse arc. In the expansion arc column mode, the arc column is immobile and the diameter of the arc column increases with the current. During this stage, the bright anode spots appear with high amplitude noise of arc voltage at high current. The expansion arc column mode plays an important role in the anode erosion. In the moving arc column mode, the average velocities were observed about 10-100 m/s, and the arc velocity increases with the increased frequency at the same current. The arc voltage expressed by arc current and frequency was obtained in this paper. The cross-section area of the arc column decreases with the increased frequency at the same current. The current density increases with the increased frequency at the certain current. Consequently, it is deduced that the arc velocity increases with the increased frequency at the same current. The mean power input concentrates in a smaller area at a higher frequency. It may be one of the reasons why the anode local melted.

Original languageEnglish
Article number65707446570744
Pages (from-to)2014-2021
Number of pages8
JournalIEEE Transactions on Power Delivery
Volume28
Issue number4
DOIs
StatePublished - 2013

Keywords

  • Arc appearance
  • arc mode
  • arc voltage
  • intermediate-frequency vacuum arc
  • transverse magnetic field (TMF)

Fingerprint

Dive into the research topics of 'Arc movement of intermediate-frequency vacuum Arc on TMF contacts'. Together they form a unique fingerprint.

Cite this