Skip to main navigation Skip to search Skip to main content

Analysis of influence of two static conductors on the interruption performance of MCCB

  • Liang Ji*
  • , Degui Chen
  • , Yingyi Liu
  • , Xingwen Li
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

Abstract

Well-designed structure of the static conductor is helpful for improving the interruption performance of MCCB. Electro-dynamic force and magnetic field of the electric arc are calculated and compared between circuit breakers using two different static conductors. Based on the calculation results, influencing factors affected by the static conductor structure, including the contact separation time, the repulsive electro-dynamic force acting on the contact, the magnetic field distribution in the electric arc and the magnetic field magnitude during arc ignition, are analyzed. According to the analysis result, improvement of the static conductor structure of an actual MCCB is carried out and found effective of improving its interruption performance by network trial.

Original languageEnglish
Pages (from-to)45-51
Number of pages7
JournalDiangong Jishu Xuebao/Transactions of China Electrotechnical Society
Volume25
Issue number8
StatePublished - Aug 2010

Keywords

  • Electro-dynamic force
  • Finite element method
  • Magnetic force
  • Molded case circuit breaker(MCCB)

Fingerprint

Dive into the research topics of 'Analysis of influence of two static conductors on the interruption performance of MCCB'. Together they form a unique fingerprint.